Event List - Mitsubishi Electric MELSEC iQ-RJ71EN71 User Manual

Melsec iq-r series cc-link ie field network
Hide thumbs Also See for MELSEC iQ-RJ71EN71:
Table of Contents

Advertisement

4.7

Event List

This section lists the events which occur in CC-Link IE Field Network.
System and operation are included in the event types.
System
Event code
Overview
00100
Link-up
00130
Receive frame error
00500
<<Own station>> Baton pass return (network entry)
00501
<<Another station>> Baton pass return (network entry)
00502
All stations baton pass normalization (network entry in all
stations)
00510
<<Own station>> Data link restart (cyclic transmission
started)
00511
<<Another station>> Data link restart (cyclic transmission
started)
00512
All stations data link normalization (cyclic transmission in
all stations started)
00513
<<Own station>> Data link start instruction acceptance
00514
<<Own station>> Data link stop instruction acceptance
00520
<<Own station>> Temporary error invalid station setting
instruction acceptance
00521
<<Own station>> Temporary error invalid station cancel
instruction acceptance
00524
<<Another station>> Temporary error invalid station setting
execution
00525
<<Another station>> Temporary error invalid station cancel
execution
00530
<<Own station>> Reserved station cancel setting
instruction acceptance
00531
<<Own station>> Reserved station enable setting
instruction acceptance
00534
<<Another station>> Reserved station cancel setting
execution
00535
<<Another station>> Reserved station enable setting
instruction execution
00540
Loopback resolution
00541
Receive parameter error resolution
00542
<<Own station>> Receive frame error line status caution
level
00543
<<Another station>> Receive frame error line status
caution level
00600
<<Own station>> Master/submaster switching occurrence
00800
Link-down
00A00
System switching request issued
00C00
<<Own station>> Baton pass interruption (departure from
network)
00C01
<<Another station>> Baton pass interruption (departure
from network)
Cause
Link-up has occurred when the network cable connected to the external device
was connected.
Receive frame error was detected. Or, the network whose network type is
different was connected.
Baton pass of the own station was returned from interruption status to normal
status.
Baton pass of another station was returned from interruption status to normal
status.
Baton pass was returned to normal status at all stations.
Data link of the own station was restarted.
Data link of another station was restarted.
Data link was returned to normal status at all stations.
Data link startup of the own station instruction was received.
Data link stop instruction of the own station was received.
Temporary error invalid station setting instruction was received.
Temporary error invalid station cancel instruction was received.
Temporary error invalid station was set at another station.
Temporary error invalid station was canceled at another station.
Reserved station cancel setting instruction was received.
Reserved station enable setting instruction was received.
Reserved station cancel setting was executed at another station.
Reserved station enable setting was executed at another station.
Loopback execution status was resolved when using a ring topology (using the
loopback function).
A parameter error received from master station/control station was resolved.
(Normal parameter was received.)
A receive frame error (line status: caution level) has been occurred.
A receive frame error (line status: caution level) has been occurred.
Master station down, or manual switching of the master and submaster station
has occurred.
Link-down occurred when network cable connected to the external device was
disconnected.
A system switching request occurred.
Baton pass of the own station was interrupted.
Baton pass of another station was interrupted.
4 TROUBLESHOOTING
279
4.7 Event List
4