Scale parameters and functions
8.13 DR 13 RS485 parameters
8.13
DR 13 RS485 parameters
8.13.1

Overview

The parameters which define the response of the RS485 interface are specified in data
record DR 13. If the interface is not used, the default values can be retained.
Procedure
● Check the parameters and modify them as required
● Transfer the data record to the scales
Table 8- 12
Assignment of data record 13
Variable
Note
Data record
Contains no. of data record
number
Length
Data record length information
Application
Information on which application
the data record belongs to
Version
Information on current data record
identifier
version
RS485 pro-
0: No protocol
tocol
1: MODBUS RTU
(Page 104)
2: SIEBERT display
RS485 baud
0: 1 200 bps
rate
1: 2 400 bps
(Page 104)
2: 9 600 bps
3: 19 200 bps
4: 38 400 bps
5: 57 600 bps
6:115 000 bps
RS485 char-
Character parity
acter parity
0: Even
(Page 105)
1: Odd
RS485 num-
Number of data bits per character
ber of data
0: 7 data bits
bits
1: 8 data bits
(Page 105)
RS485 num-
Number of stop bits
ber of stop
0: 1 stop bit
bits
1: 2 stop bits
(Page 105)
Bit 3
Reserve
Bit 4
Reserve
Bit 5
Reserve
Bit 6
Reserve
Bit 7
Reserve
Bit 8
Reserve
Bit 9
Reserve
102
Type
Length
Rw
(bytes)
USHORT
2
r
USHORT
2
r
USHORT
2
r
USHORT
2
r
USHORT
2
rw
USHORT
2
rw
BIT
0
rw
BIT
0
rw
BIT
0
rw
BIT
0
rw
BIT
0
rw
BIT
0
rw
BIT
0
rw
BIT
0
rw
BIT
0
rw
BIT
0
rw
Default
Min.
Max.
13
-
-
24
-
-
101
-
-
1
1
65635
1
0
2
3
0
6
0
0
1
0
0
1
0
0
1
0
0
1
0
0
1
0
0
1
0
0
1
0
0
1
0
0
1
0
0
1
Manual, 07/2014, A5E31238908A-02
Modbus
registers
1558
1559
1560
1561
1562
1563
1564.16
1564.15
1564.14
1564.13
1564.12
1564.11
1564.10
1564.9
1564.8
1564.7
SIWAREX WP231