9.9

G(P).RDMSG

These instructions read/write parameters from the master station to the remote device station and read out the status.
(A master/local module with a serial number (first five digits) of 10032 or later supports these instructions.)
The instructions can be used with the remote device station, for example NZ2AW1C2AL, that supports the message
transmission function.
[Instruction
[Execution
symbol]
condition]
G.RDMSG
GP.RDMSG
Setting
Internal device
data
(System, user)
Bit
Word
(S1)
(S2)
(D1)
(D2)
(1) Setting data
*1
Device
Start I/O number of the module (First two digits of I/O number written
Un
with three digits)
(S1)
Start number of the device in which control data is stored
*2
Start number of the device that stores data to be sent
(S2)
*2
Start number of the device that stores received data
(D1)
Device that turns on for one scan upon completion of reading.
(D2)
(D2) + 1 also turns on at an abnormal end.
*1
The local device and the file register of each program cannot be used as a device for setting data.
*2
For details of the send data and receive data, refer to the manual for the remote device station that supports the
message transmission function.
Command
G.RDMSG
Command
GP.RDMSG
Applicable device
Link direct
device
File
J\
register
Bit
Word
Description
CHAPTER 9 DEDICATED INSTRUCTIONS
Un
(S1)
(S2)
Un
(S1)
(S2)
Intelligent
function module
Index
device
register Z
U\G
Setting range
0 to FE
Within the range of the
specified device
Within the range of the
specified device
Within the range of the
specified device
Within the range of the
specified device
(D1)
(D2)
(D1)
(D2)
Constant
Others
K, H
$
Data type
16-bit binary
H
Device name
Bit
221
9