Siemens SIMOTICS M-1PH818 Operating And Installation Instructions page 72

Main motors
Table of Contents

Advertisement

Electrical connection
6.2 Connecting
3. Fasten the cable lug to the end of the conductor correctly, e.g. by crimping.
4. If necessary, insulate the cable lugs in order to maintain the minimum clearances of 10 mm
Connection using a cable lug at terminal boxes 1XB7 322 / 1XB7 422
Connection using a cable lug at terminal boxes 1XB7 700 / 1XB7 712
72
and the 20 mm creepage distance, which are normally available.
The tightening torque for contact nuts and fixing screws depends on the size of the screw,
see Case A in the table in Chapter Tightening torques for screw and bolt connections
(Page 163).
Customer connecting cable
Internal motor connecting cable
Copper spacer ring
Customer connecting cable
Connection bar
SIMOTICS M-1PH8 1PH818., 1PH822., 1PH828.
Operating Instructions 10/2017