main terminal
ground terminal
Table 6-2
Data for electrical connection
Terminal box type
Cable entry
Max. poss. cable outer diameter
Number of main terminals
Max. cross-section per terminal
Max. current per terminal
Number of ground terminals
Current carrying capacity based on IEC / EN 60204-1 or IEC / EN 60364-5-32
6.2.5

Connection with cable lugs

1. To connect the cables to the main terminals, select cable lugs that match the necessary
2. Remove the insulation from the conductor ends so that the remaining insulation is almost
SIMOTICS M-1PH8 1PH818., 1PH822., 1PH828.
Operating Instructions 10/2017
1XB7 700
1XB7 322
2 x M50 x 1.5
38 mm
3 x M12
2 x 50 mm
210 A
4 x M6
cable cross-section and appropriate screw size.
The connectable cable cross section is determined by the cable lug size for example.
– Cable lug in accordance with DIN 46234 from 35 mm
– Cable lug in accordance with DIN 46235 from 35 mm
Observe the possible outer diameter of the connecting cable in the chapter entitled
"Electrical connection data".
Connect only one conductor per cable lug.
long enough to reach the cable lug.
signal connection terminal
signal connection
1XB7 422
2 x M63 x 1.5
53 mm
3 x M12
2 x 70 mm
2
2
270 A
4 x M8
Electrical connection
6.2 Connecting
1XB7 712 (*)
1XB7 700
1XB7 712 (*)
3 x M75 x 1.5
4 x M75 x 1.5
68 mm
68 mm
3 x 3 x M12
3 x 4 x M16
3 x 150 mm
4 x 185 mm
2
700 A
1150 A
Terminal strip
4 x M16
to 185 mm
,
2
2
to 185 mm
.
2
2
2
71