List of status codes (no error)
o_wDiagCode
State name
(Hexadecimal)
0000H
Idle
8001H
Init
8010H
Output Disable
8000H
Output Enable
WARNING
Please do the above actions when the FB detects an error or is in an unexpected state. However, when the situation is still not corrected, please check the
following.
• A failure in safety devices and emergency stop devices
• Wiring and status of a safety remote I/O module and a safety programmable controller
• Programming logic, the memory allocation of safety devices, and the connections of safety FB variables
• Setting of i_bS_StartReset
4 SAFETY FB SPECIFICATIONS
28
4.3 M+SF_EDM_R
Description, output setting
The FB is not active. (Initial state)
• o_bReady: OFF
• o_bS_EDM_Out: OFF
• o_bError: OFF
The FB activation startup inhibit is active.
(i_bS_Starti_bReset=OFF)
• o_bReady: ON
• o_bS_EDM_Out: OFF
• o_bError: OFF
EDM control is not active. Timer starts when state is entered.
• o_bReady: ON
• o_bS_EDM_Out: OFF
• o_bError: OFF
EDM control is active. Timer starts when state is entered.
• o_bReady: ON
• o_bS_EDM_Out: OFF
• o_bError: OFF
Action
Initialize the FB by setting i_bActivate to
ON.
Set i_bReset to ON.
Set i_bS_OutControl to ON.
None.