A.11

Technical data: LOGO! AM2 PT100

Power supply
Input voltage
Permissible range
Power consumption
Voltage failure buffering
Power loss at
Electrical isolation
Reverse polarity protection
Ground terminal
Sensor inputs
Number
Type
Connection of sensors
Measurement range
Settings for the measurement display on
the LOGO! Basic:
Curve linearization
Measuring current Ic
Measurement rate
Resolution
Error limits
Electrical isolation
Cable length (shielded)
Interference frequency
suppression
LOGO!
Manual, 10/2017, A5E01248535-AA
12 V
24 V
2-wire technique
3-wire technique
1 °C steps
0.25 °C steps
(rounded to one decimal)
1 °F steps
0.25 °F steps
(rounded to one decimal)
0 °C ... +200 °C
-50 °C ... +200 °C
A.11 Technical data: LOGO! AM2 PT100
LOGO! AM2 PT100
12/24 V DC
10.8 ... 28.8 V DC
25 ... 50 mA
typ. 5 ms
0.3 ... 0.6 W
0.6 ... 1.2 W
No
Yes
for connecting ground and shielding of the measuring
line
2
RTD PT100
Yes
Yes
-50 °C... +200 °C
-58 °F ... +392 °F
Offset: -50, Gain: 0.25
Offset: -500, Gain: 2.50
Offset: -58, Gain: 0.45
Offset: -580, Gain: 4.50
No
1.1 mA
depends on the installation
typical: 50 ms
0.25 °C
of the final measured value:
±1.0 %
± 1.5 %
No
max. 10 m
55 Hz
Technical data
263