Technical data

A.2 Technical data: LOGO! 230...

Shock
Free fall (packaged)
Electromagnetic compatibility (EMC)
Noise emission
Electrostatic discharge
Electromagnetic fields
HF currents on cables and cable
shielding
Burst pulses
High-energy surge pulse (applies only
to LOGO! 230 ...)
Safety to IEC
Clearance and creepage distance
rating
Insulation strength
Cycle time
Cycle time per function
Startup
Startup time at power-up
A.2

Technical data: LOGO! 230...

Power supply
Input voltage
Permissible range
Permissible mains frequency
246
Criterion
IEC 60068-2-27
IEC 60068-2-32
EN 55011/A
EN 55022/B
EN 50081-1
(domestic area)
IEC 61000-4-2
Severity 3
IEC 61000-4-3
IEC 61000-4-6
IEC 61000-4-4Severity 3
IEC 61000-4-5Severity 3
IEC 60664, IEC 61131-2,
EN 50178
cULus to UL 508, CSA
C22.2 No. 142
With LOGO! 230 R/RC,
also IEC60730-1
IEC 61131-2
Tested in accordance with
LOGO! 230RC
LOGO! 230RCo
115...240 V AC/DC
85 ... 265 V AC
100 ... 253 V DC
47 ... 63 Hz
Values
18 shocks
(half-sine wave 15g/11 ms)
0.3 m
Limit class B group 1
8 kV air discharge
6 kV contact discharge
Field strength 1 V/m and 10
V/m
10 V
2 kV (supply and signal lines)
1 kV (power lines) symmetrical
2 kV (power lines) asymmetrical
Fulfilled
Fulfilled
< 0.1 ms
typ. 9 s