Vent Line Sizing Reference - Trane CVHE Installation, Operation And Maintenance Manual

Water-cooled centravac chillers with tracer adaptiview control
Table of Contents

Advertisement

Vent Line Sizing Reference

Table 12. "C" values used to determine rupture disk
vent line sizes; for use with the following
figure
"C" Values for Unit Components
Evap.
Cond.
Total
Size
Size
"C"
(EVSZ)
(CDSZ)
Value
032S
032S
50.00
032S
032L
61.32
032L
032L
65.09
050S
050S
64.20
050S
050L
72.10
050L
050L
83.17
050S
080S
69.71
050L
080L
90.52
080S
080S
86.48
080S
080L
96.22
080L
080L
111.50
080L
142L
117.53
142M
142L
127.49
142L
142L
134.89
142E
142L
143.11
210L
210L
149.91
CVHE-SVX02M-EN
Short
Long H.
Free
Aux.
H.R.
R.
Cooling
Cond.
Cond.
Cond.
Econ.
18.87
25.19
15.30
23.55
31.45
15.30
N/A
N/A
N/A
29.06
38.80
15.30
N/A
N/A
N/A
51.01
56.80
15.30
Table 12. "C" values used to determine rupture disk
vent line sizes; for use with the following figure
(continued)
Evap.
Cond.
Size
Size
(EVSZ)
(CDSZ)
250E
250L
210D
210D
250D
250D
3.66
250M
250M
250X
250X
Notes:
5.50
1.
Rupture disk diameter is 3 in. (76.2 mm), with the exception of
250E evaporator/250L condenser units with heat recovery which
have a rupture disk diameter of 4 in. (101.6 mm).
2.
To determine the total "C" value for a specific unit, add the
appropriate "C" values for the evaporator, standard condenser, and
N/A
economizer. If the unit is equipped with any options (e.g., heat
recovery, free cooling, or an auxiliary condenser), add the
applicable "C" values to this total. With this new sum, refer to the
following figure to determine the vent-line pipe diameter.
5.38
3.
If piping multiple rupture disks to a common vent line, first
determine the total "C" value for each rupture disk, then add all "C"
values together and apply the result to the following figure.
N/A
4.
RuptureGuard™ size based on "C" value:
3-in. (76.2 mm) valve: "C" value 0 to 104.20
4-in. (101.6 mm) valve: C value 104.21 to 223.9
RuptureGuard™ is not available for 250E evaporator/250L
7.13
condenser units with heat recovery.
V V e e n n t t P P i i p p i i n n g g
"C" Values for Unit Components
Total
Short
Long H.
Aux.
"C"
H.R.
R.
Cond.
Value
Cond.
Cond.
175.74
N/A
62.12
15.30
112.93
15.30
122.62
N/A
N/A
146.36
15.30
164.74
Free
Cooling
Econ.
N/A
7.13
N/A
41

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

CvhfCvhgCvhe-svx02m-en