Unit Clearances and Weights

Recommended Unit Clearances

Adequate clearances around and above the chiller are
required to allow sufficient access for service and
maintenance operations. Specific unit clearance
requirements are indicated in the submittal package
provided for your unit.
Do NOT install piping or conduit above the
compressor motor assembly or behind the suction
elbow of the unit.
Minimum vertical clearance above the unit is 3 ft
(92 cm).
Figure 4. Clearance requirements
Table 1. Clearance requirements
Evaporator Size
Shell Combo
Short/Short
032 Short/Long
Short/Long
Long/Long
Short/Short
050 Short/Long
Short/Long
Long/Long
Short/Short
080 Short/Long
Short/Long
CVHE-SVX02M-EN
A
B
cm
in.
in.
45
114
141
77
195
219
45
114
187
45
114
141
78
198
219
45
114
187
53
134
141
85
215
219
Use a housekeeping pad to provide better service
clearances; refer to submittal for more information.
Per National Electric Code (NEC) Article 110: Unit
mounted starters from 0 to 600V require a 42 inch
(107 cm) clearance, 601 to 2500V require a 48 inch
(122 cm) clearance, and 2501 to 9000V require a 60 inch
(152 cm) clearance. Refer to NEC and local electrical
codes for starter and control panel clearance
requirements.
C
cm
cm
in.
358
321
815
556
431
1094
474
411
1043
358
321
815
556
431
1094
474
411
1043
358
329
835
556
439
1115
D
E
cm
in.
in.
34
86
53
34
86
53
34
86
53
40
101
62
40
101
62
40
101
62
36
91
76
36
91
76
cm
134
134
134
157
157
157
193
193
15