Leveling The Unit - Trane CVHE Installation, Operation And Maintenance Manual

Water-cooled centravac chillers with tracer adaptiview control
Table of Contents

Advertisement

I I n n s s t t a a l l l l a a t t i i o o n n : : M M e e c c h h a a n n i i c c a a l l
Figure 8. Chiller foot and isolator orientation
Figure 9. Leveling the chiller
N N o o t t e e : : Use of a laser level is an acceptable alternative
method to level the unit.
26
I I m m p p o o r r t t a a n n t t : : Do NOT install spring isolators or brackets
in such a way that they could inhibit chiller
servicing such as charging or evacuation,
oil tank service, etc.

Leveling the Unit

The chiller must be set level within 1/16 in. (1.6 mm).
1. Measure and make a punch mark an equal distance
up from the bottom of each foot of the chiller.
2. Suspend a clear plastic tube along the length of the
chiller as shown in the following figure.
3. Fill the tube with water until the level aligns with
the punch mark at one end of the chiller.
4. Check the water level at the opposite mark. If the
water level does not align with the punch mark, use
full length shims to raise one end of the chiller until
the water level at each end of the tube aligns with
the punch marks at both ends of the chiller.
5. Once the unit is level across its length, repeat the
first three steps to level the unit across its width.
I I m m p p o o r r t t a a n n t t : : Immediately report any unit damage
incurred during handling or installation at
the job site to the Trane sales office.
CVHE-SVX02M-EN