Free Cooling Cycle - Trane CVHE Installation, Operation And Maintenance Manual

Water-cooled centravac chillers with tracer adaptiview control
Table of Contents

Advertisement

S S t t a a r r t t - - u u p p a a n n d d S S h h u u t t - - d d o o w w n n
Figure 57. Sequence of operation: ice making: stopped to ice to ice building complete

Free Cooling Cycle

Based on the principle that refrigerant migrates to the
coldest area in the system, the free cooling option
adapts the basic chiller to function as a simple heat
exchanger. However, it does not provide control of the
leaving chilled water temperature.
If condenser water is available at a temperature lower
than the required leaving chilled water temperature,
the operator interface must remain in AUTO and the
operator starts the free cooling cycle by enabling the
Free Cooling mode in the Tracer® AdaptiView™
Feature Settings group of the operator interface, or by
means of a BAS request. The following components
must be factory- or field-installed to equip the unit for
free cooling operation:
a refrigerant gas line, and electrically-actuated
shutoff valve, between the evaporator and
condenser,
a valved liquid return line, and electrically-actuated
shutoff valve, between the condenser sump and the
evaporator,
a liquid refrigerant storage vessel (larger
economizer), and
additional refrigerant.
78
When the chiller is changed over to the free cooling
mode, the compressor will shut down if running and
the shutoff valves in the liquid and gas lines open; unit
control logic prevents the compressor from energizing
during free cooling. Liquid refrigerant then drains (by
gravity) from the storage tank into the evaporator and
floods the tube bundle. Since the temperature and
pressure of the refrigerant in the evaporator are higher
than in the condenser (i.e., because of the difference in
water temperature), the refrigerant in the evaporator
vaporizes and travels to the condenser, cooling tower
water causes the refrigerant to condense on the
condenser tubes, and flow (again, by gravity) back to
the evaporator.
This compulsory refrigerant cycle is sustained as long
as a temperature differential exists between condenser
and evaporator water. The actual cooling capacity
provided by the free cooling cycle is determined by the
difference between these temperatures which, in turn,
determines the rate of refrigerant flow between the
evaporator and condenser shells.
If the system load exceeds the available free cooling
capacity, the operator must manually initiate
changeover to the mechanical cooling mode by
disabling the free cooling mode of operation. The gas
and liquid line valves then close and compressor
operation begins (refer to
Figure 51, p.
73, beginning at
CVHE-SVX02M-EN