9.3.6 Branch component layout (standard circuit)

Branch component layout (standard circuit)
Soft starter
Nominal
current
Soft starter
G1
Type
A
3RW44 22
29
3RW44 23
36
3RW44 24
47
3RW44 25
57
3RW44 26
77
3RW44 27
93
3RW44 34
113
3RW44 35
134
3RW44 36
162
3RW44 43
203
3RW44 44
250
3RW44 45
313
3RW44 46
356
3RW44 47
432
Branch component layout (standard circuit)
Soft starter
Nominal
current
Soft starter
G1
Type
A
3RW44 22
29
3RW44 23
36
3RW44 24
47
3RW44 25
57
3RW44 26
77
3RW44 27
93
3RW44 34
113
3RW44 35
134
3RW44 36
162
3RW44 43
203
3RW44 44
250
3RW44 45
313
3RW44 46
356
3RW44 47
432
1) If the "combined braking" stopping function is selected, no brake contactor is necessary.
If the "DC braking" stopping function is selected, a brake contactor must be additionally used (refer to table for types)
The "DC braking" function is recommended for applications with larger centrifugal masses (J
2) Additional K4 auxiliary relay, for device type 3RW44 26 and larger:
LZX:RT4A4T30
(3RW44 soft starter with 230 V AC rated control supply voltage),
LZX:RT4A4S15
(3RW44 soft starter with 115 V AC rated control supply voltage).
SIRIUS 3RW44 manual
GWA 4NEB 535 2195-02 DS 01
Circuit breaker
Conductor protection fuse
Current
Q1
F1
Type
A
Type
3RV10 42-4HA10
50
3NA3 820-6
3RV10 42-4JA10
63
3NA3 822-6
3RV10 42-4KA10
75
3NA3 824-6
3RV10 42-4LA10
90
3NA3 830-6
3RV10 42-4MA10
100
3NA3 132-6
3RV10 42-4MA10
100
3NA3 136-6
3VL17 16-2DD36
160
3NA3 244-6
3VL17 16-2DD36
160
3NA3 244-6
3VL37 25-2DC36
250
3NA3 365-6
3VL47 31-3DC36
315
2 x 3NA3 354-6
3VL47 31-3DC36
315
2 x 3NA3 354-6
3VL47 40-3DC36
400
2 x 3NA3 365-6
3VL47 40-3DC36
400
2 x 3NA3 365-6
3VL57 50-3DC36
500
2 x 3NA3 365-6
Semiconductor fuse, minimum
Size
Current
F3
Type
A
3NE4 120
0
80
3NE4 121
0
100
3NE4 121
0
100
3NE4 122
0
125
3NE4 124
0
160
3NE3 224
1
160
3NE3 225
1
200
3NE3 225
1
200
3NE3 227
1
250
3NE3 230-0B
1
315
3NE3 230-0B
1
315
3NE3 233
1
450
3NE3 333
2
450
3NE3 335
2
560
Size
Current
A
00
50
00
63
00
80
00
100
1
125
1
160
2
250
2
250
3
500
3
2 x 355
3
2 x 355
3
2 x 500
3
2 x 500
3
2 x 500
Semiconductor fuse, maximum
Size
Current
F3
Type
A
3NE4 121
0
100
3NE4 122
0
125
3NE4 122
0
125
3NE4 124
0
160
3NE4 124
0
160
3NE3 333
2
450
3NE3 335
2
560
3NE3 335
2
560
3NE3 333
2
450
3NE3 333
2
450
3NE3 333
2
450
3NE3 336
2
630
3NE3 336
2
630
3NE3 338-8
2
800
> J
load
General technical data
Full-range fuse
Size
Current
F1'
Type
A
3NE1 020-2
00
80
3NE1 020-2
00
80
3NE1 021-2
00
100
3NE1 022-2
00
125
3NE1 022-2
00
125
3NE1 224-2
1
160
3NE1 225-2
1
200
3NE1 227-2
1
250
3NE1 227-2
1
250
3NE1 230-2
1
315
3NE1 331-2
2
350
3NE1 333-2
2
450
3NE1 334-2
2
500
3NE1 435-2
3
560
Line contactor
Braking contactor
up to 400 V
(option)
K1/K1A
K2
Type
Type
3RT10 34
3RT15 26
3RT10 35
3RT15 26
3RT10 36
3RT15 35
3RT10 44
3RT15 35
3RT10 45
3RT10 24
3RT10 46
3RT10 25
3RT10 54
3RT10 34
3RT10 55
3RT10 36
3RT10 56
3RT10 44
3RT10 64
3RT10 44
3RT10 65
3RT10 44
3RT10 75
3RT10 54
3RT10 75
3RT10 54
3RT10 76
3RT10 55
).
motor
Voltage
V
690 +5 %
690 +5 %
690 +5 %
690 +5 %
690 +5 %
690 +5 %
690 +5 %
690 +5 %
690 +5 %
600 +10 %
460 +10 %
690 +5 %
690 +5 %
690 +5 %
1)2)
K3
Type
3RT10 35
3RT10 36
3RT10 44
3RT10 45
3RT10 45
3RT10 54
3RT10 55
3RT10 56
3RT10 56
3RT10 64
9-15