Commissioning

5.4.7 Parameterization of the inputs

4
Inputs
Select
ESC
OK
1
Input 1 -
Action
Motor right PS1
Change
ESC
OK
2
Input 2 -
Action
No action
Change
ESC
OK
3
Input 3 -
Action
No action
Change
ESC
OK
4
Input 4 -
Action
Trip/Reset
Change
ESC
OK
Fig. 5-22: Parameterization of the inputs

5.4.8 Parameterization of the outputs

5
Outputs
Select
ESC
OK
1
Output 1 -
Action
On-time
Change
ESC
OK
2
Output 2 -
Action
No action
Change
ESC
OK
3
Output 3 -
Action
No action
Change
ESC
OK
4
Output 4 -
Action
Group error
Change
ESC
OK
Fig. 5-23: Parameterization of the outputs
5-20
Parameterization options for
control inputs 1 ... 4
No action
Manual operation local
Slow speed
Trip/Reset
Motor right parameter set 1
Motor left parameter set 1
Motor right parameter set 2
Motor left parameter set 2
Motor right parameter set 3
Motor left parameter set 3
Emergency start
Quick stop
Parameterization options
for relay outputs 1 ... 3
No action
PIO output 1
PIO output 2
Input 1
Input 2
Input 3
Input 4
Run up
Bypass operation
Coasting down
On time motor
Command motor-on
DC brake contactor
Group warning
Group error
Device error
Power on
Ready to start
Notice
The parameters "motor left parameter set 1/2/3" are
active only when the "slow speed" parameter is active at
the same time.
Directions of rotation:
Right: rotation in line phase direction
Left: rotation against line phase direction
If one action is assigned to two inputs, both of the inputs
must be connected to carry out the selected function
(e.g. to obtain logical "AND" linking for a start command,
assign the "motor right PS1" function to input 1 and 2. A
start command is only accepted if both inputs are
active.).