Motor overload
protection
6-18
The motor overload protection is based on the motor winding temperature. This
temperature is used to determine whether the motor is overloaded or is
operating within its normal rating.
The winding temperature can either be calculated using the integrated
electronic motor overload function, or be measured using a connected motor
thermistor.
Both versions must be combed (=activated) to obtain the so-called full motor
protection.
The current flow during motor operation is measured using current
measurement at the converters in the soft starter. The temperature rise of the
winding is calculated based on the configured rated operating current of the
motor.
Depending on the set tripping class (class setting) and protection parameters, a
warning or a trip is generated when the characteristic curve is touched.