10.3.7 Branch Component Layout (Inside Delta Circuit)

Inside-delta circuit fused version with 3NE or 3NC SITOR fuses
(semiconductor protection by fuse, lead and overload protection by circuit-breaker)
Q1
F3
Q11
Soft starters
Semiconductor fuses, minimum
Rated
current
Q11
F3
Type
A
Type
1)
Type of coordination 2
3RW44 22 50
3NE4 120
3RW44 23 62
3NE4 121
3RW44 24 81
3NE4 121
3RW44 25 99
3NE4 122
3RW44 26 133
3NE4 124
3RW44 27 161
3NE3 224
3RW44 34 196
3NE3 225
3RW44 35 232
3NE3 225
3RW44 36 281
3NE3 227
3RW44 43 352
3NE3 230-0B
3RW44 44 433
3NE3 230-0B
3RW44 45 542
3NE3 233
3RW44 46 617
3NE3 333
3RW44 47 748
3NE3 335
3RW44 53 954
2 x 3NE3 335
3RW44 54 1065
2 x 3NE3 335
3RW44 55 1200
2 x 3NE3 335
3RW44 56 1351
2 x 3NE3 336
3RW44 57 1524
2 x 3NE3 336
3RW44 58 1680
2 x 3NE3 336
3RW44 65 1864
2 x 3NE3 340-8 900
3RW44 66 2103
2 x 3NE3 340-8 900
Soft starter
Line contactors
up to 400 V
Rated
(optional)
current
Q11
Q21
Type
A
Type
1)
Type of coordination 2
3RW44 22 50
3RT10 36-1AP04
3RW44 23 62
3RT10 44-1AP04
3RW44 24 81
3RT10 46-1AP04
3RW44 25 99
3RT10 54-1AP36
3RW44 26 133
3RT10 55-6AP36
3RW44 27 161
3RT10 56-6AP36
3RW44 34 196
3RT10 64-6AP36
3RW44 35 232
3RT10 65-6AP36
3RW44 36 281
3RT10 66-6AP36
3RW44 43 352
3RT10 75-6AP36
3RW44 44 433
3RT10 76-6AP36
3RW44 45 542
3TF68 44-0CM7
3RW44 46 617
3TF68 44-0CM7
3RW44 47 748
3TF69
3RW44 53 954
2 x 3TF68 44-0CM7
3RW44 54 1065
2 x 3TF68 44-0CM7
3RW44 55 1200
2 x 3TF69 44-0CM7
3RW44 56 1351
2 x 3TF69 44-0CM7
3RW44 57 1524
2 x 3TF69 44-0CM7
3RW44 58 1680
3RW44 65 1864
3RW44 66 2103
1) The types of coordination are explained in more detail in the Technical information LV 1 T under – Fuseless Load Feeders.
10-22
M
3~
Rated current
Size
A
80
0
100
0
100
0
125
0
160
0
160
1
200
1
200
1
250
1
315
1
315
1
450
1
450
2
560
2
560
2
560
2
560
2
630
2
630
2
630
2
2
2
Circuit-breakers
440 V +10 %
Q1
Type
3RV10 4.-4KA10
3RV10 4.-4LA10
3RV10 4.-4MA10
3VL27 16-.DC36
3VL27 16-.DC36
3VL37 20-.DC36
3VL37 25-.DC36
3VL47 31-.DC36
3VL47 40-.DC36
3VL47 40-.DC36
3VL57 50-.DC36
3VL57 63-.DC36
3VL67 80-.AB36
3VL67 80-.AB36
3VL77 10-.AB36
3VL77 12-.AB36
3VL87 16-.AB36
3VL87 16-.AB36
3VL87 16-.AB36
3WL12 20
3WL12 25
3WL12 25
F1
Q21
F3
Q11
M
3~
Semiconductor fuses, maximum
Rated current
F3
Type
A
3NE4 121
100
3NE4 122
125
3NE4 122
125
3NE4 124
160
3NE4 124
160
3NE3 333
450
3NE3 335
560
3NE3 335
560
3NE3 333
450
3NE3 333
450
3NE3 333
450
3NE3 336
630
3NE3 336
630
3NE3 338-8
800
3 x 3NE3 334-0B 500
3 x 3NE3 334-0B 500
3 x 3NE3 334-0B 500
2 x 3NE3 340-8
900
3 x 3NE3 340-8
900
3 x 3NE3 340-8
900
3 x 3NE3 338-8
800
3 x 3NE3 338-8
800
Line protection, maximum
Rated
690 V +5 %
current
F1
A
Type
75
3NA3 824-6
90
3NA3 830-6
100
3NA3 132-6
160
3NA3 136-6
160
3NA3 240-6
200
3NA3 244-6
250
3NA3 360-6
315
3NA3 360-6
400
2 x 3NA3 360-6
400
2 x 3NA3 365-6
500
2 x 3NA3 365-6
800
3 x 3NA3 365-6
800
3 x 3NA3 365-6
800
3 x 3NA3 365-6
1000
3 x 3NA3 365-6
1250
3 x 3NA3 365-6
1600
3 x 3NA3 365-6
1600
3 x 3NA3 372
1600
3 x 3NA3 372
2000
2 x 3NA3 480
2500
2 x 3NA3 482
2500
2 x 3NA3 482
Semiconductor fuses (cylinder)
Size
Rated current
F3
Type
A
0
3NC2 280
80
0
3NC2 200
100
0
3NC2 200
100
0
0
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Rated
current
A
80
100
125
160
200
250
400
400
2 x 400
2 x 500
2 x 500
3 x 500
3 x 500
3 x 500
3 x 500
3 x 500
3 x 500
3 x 630
3 x 630
2 x 1000
2 x 1250
2 x 1250
SIRIUS 3RW44 System Manual
GWA 4NEB 535 2195-02 DS 04
Size
22 x 58
22 x 58
22 x 58
Size
00
00
1
1
2
2
3
3
3
3
3
3
3
3
3
3
3
3
3
4
4
4