5.4.5 Setting slow speed parameters

5.4.6 Determining current limits

SIRIUS 3RW44 manual
GWA 4NEB 535 2195-02 DS 01
4
Slow-speed
parameters
Select
ESC
OK
1
Slow speed
factor right
7
Change
ESC
OK
3
Slow
torque right
80.0 %
Change
ESC
OK
2
Slow speed
factor left
7
Change
ESC
OK
4
Slow
torque left
80.0 %
Change
ESC
OK
Fig. 5-20: Selection of slow speed settings
5
Current limit
values
Select
ESC
OK
1
Minimum cur-
rent limit
Deactivated
Change
ESC
OK
2
Maximum cur-
rent limit
Deactivated
Change
ESC
OK
Fig. 5-21: Determining current limits
Adjustable
from ... to
Notice
To control the motor with the specified slow
speed parameters, "slow speed" must be
3 ... 21 %
assigned to one control input, and "motor
right PS1/2/3" or "motor left PS1/2/3" must
be assigned to the other control input. Also
refer to circuit suggestion in 8.1.7.
20 ... 100 %
Directions of rotation:
Right: rotation in line phase direction
3 ... 21 %
Left: rotation against line phase direction
20 ... 100 %
Adjustable
from ... to
19 ... 100 %
50 ... 150 %