Siemens Sirius 3RW44 System Manual page 55

Hide thumbs Also See for Sirius 3RW44:
Table of Contents

Advertisement

Starting mode: torque control
2
Starting
settings
Select
ESC
OK
1
Starting mode
Torque control
Change
ESC
OK
3
Start torque
50.0 %
Change
ESC
OK
4
Limiting
torque
150 %
Change
ESC
OK
5
Starting time
20 s
Change
ESC
OK
6
Maximum
starting time
Deactivated
Change
ESC
OK
8
Breakaway
voltage
80 %
Change
ESC
OK
9
Breakaway time
0 ms
Change
ESC
OK
Fig. 5-10: Torque control
SIRIUS 3RW44 manual
GWA 4NEB 535 2195-02 DS 01
Adjustable
Motor
from ... to
torque (M)
10 ... 100 %
Breakaway voltage
20 ... 200 %
Limiting torque
Start torque
0 ... 360 s
1 ... 1000 s
M
1
Direct on-line starting
(maximum torque to be generated)
4_3_Drehmomentrampe.wmf
40 ... 100 %
0 ... 2000 ms
Nm
1
M
Nom
Breakaway time
Starting time
Maximum starting time
Commissioning
Time (t)
s
5-13