9.7.5

Parameterizing F-output modules

Procedure
To configure the inserted F-output modules, select them successively and make the settings
individually for each module in the inspector window. Proceed as follows:
1. In the device view, select the rack and open the device overview.
2. In the device overview, select on the rack one of the modules to be configured.
3. In the "Properties" inspector window, select the "I/O address" entry.
4. Enter the desired address in the "Input addresses > Start address" field. Note the
following:
– The I/O addresses must lie within the process image of the PLC (default setting: 1024
– Do not use any I/O addresses that are used for some other purpose, e.g. by the
5. In the "Properties" inspector window, select the "DO parameters" entry.
The properties will be displayed. Safety-relevant settings are marked yellow.
6. Make the required settings, e.g.
– Enter the desired value (in ms) under "Read-back time". This time should be set to at
– "Diagnosis: Wire breakage" should be activated
SINUMERIK STEP 7 Toolbox V14 SP1
Configuration Manual, 05/2017, A5E41846325
bytes; can be configured under "Cycle" in the PLC properties).
machine control panel.
least 200 ms for large capacitive or inductive loads.
Safety configuration
9.7 Configuring Safety Integrated (SPL)
183