<Example of operation>
1) Output terminal function: 28 (OT) Over-torque detection
Over-torque
signal output
-
6
6.16.10 Cooling fan control selection
: Cooling fan ON/OFF control
Function
=: Cooling fan automatically controlled. Cooling fan operates only when the ambient temperature is
=: Cooling fan not automatically controlled. Fan is always running when the inverter is on.
If the ambient temperature is high, even when the inverter is stopped, the cooling fan automatically
[Parameter setting]
Cooling fan ON/OFF control
= (Alarm only)
Torque (%)
When = (tripping), the inverter will trip if over-torque lasts for the period of time set with
. In such a case, the over-torque signal remains ON.
Set to operate the fan only when the ambient temperature is high during operation. When the inverter
is on, the service life of the cooling fan is longer than if it is always running.
high during operation.
operates.
Title
Function
less than
Time [sec]
Adjustment range
0: ON/OFF control
1: Always ON
F-50
E6581595
OFF
ON
OFF
Default setting
0