7.3.3
Settings depending on voltage (0 to 5 V) input
<external potentiometer>
You can set the frequency by connecting the FRH kit (optional), or a potentiometer (1 to 10kΩ – 1/4W) to the VI
terminal.
Connect the potentiometer between the P5, VI, and CC terminals. The standard voltage for the P5 terminal is 5Vdc.
Instead of using the potentiometer, you can set the frequency settings by inputting an analog voltage signal of 0
to 5Vdc between the VI and CC terminals.
The following shows examples when the run command is input from the terminal.
Title
Function
 Command mode selection
Frequency setting mode

selection
Analog/logic input selection

(VI terminal)
 VI input point 1 setting
 VI input point 1 frequency
 VI input point 2 setting
 VI input point 2 frequency
 Analog input filter
*Depends upon the setup menu settings. Refer to section 11.5.
MCCB
R/L1
Power
S/L2
Supply
T/L3
* Connect a single-phase
input model to R/L1 and
S/L2/N.
FLA
FLB
FLC
P24
OUT
NO
CC
 = : Voltage signal input (0 – 5V)
Adjustment range
0 - 2
0 - 5
0: Voltage signal input (0 - 10V)
1: Current signal input (4 - 20mA)
2: Logic input
3: Voltage signal input (0 - 5V)
0 - 100%
0.0 - 400.0Hz
0 - 100%
0.0 - 400.0Hz
4 - 1000 ms
U/T1
VF-nC3
V/T2
W/T3
S1
S2
Forward
run
F
Reverse
R
run
FM
CC
VI
P5
1 to 10 kΩ - 1/4 W
G-13
Default setting
1
(panel keypad)
2
(setting dial)
0
0
0.0
100
*
64
 Run and stop settings
Motor
You can switch between forward run (F)
and reverser run (R), and run/stop with
IM
external signals.
 Setting characteristics for the
frequency setting signal and operation
frequency
Set characteristics at two points in the
diagram below.
 Connecting and calibrating the
frequency meter
Select the type of meter connected at
 and calibrate.
 Refer to section 3.4 for details.
Hz

Point 1


0%
(0 V
Frequency setting signal
E6581595
Setting example
0
(terminal board)
0
(terminal board VI)
3
(Voltage signal
(0 - 5V))
0
0.0
100
60.0
64
7
Point 2
%

100%
to
5 V)