Panasonic S-36PU1E5A Service Manual page 409

Table of Contents

Advertisement

(3) Fit the decorative panel and ceiling wall together, making sure that there is no gap between the two.
Readjust indoor unit height, if there is a gap between ceiling wall and decorative panel.
Example of PROPER installation
Air
Fit the insulator (this part) and be
careful for cool air leakage.
(4) Open the indoor control box cover. (3 pcs. screws)
(5) Insert firmly the connector of cosmetic louver to indoor
PCB LM and WL.
Be caution not to clamp the cord in between control
board and control board cover.
(6)
After completing the aforementioned, install the removed
part by reversing the steps for removal.
WARNING
Be sure to hook the air inlet grille string, to prevent grille
from falling and causing injury from it.
Hang the
string
Air inlet grille
6-10-3. When Using Wireless Remote Controller Instead of Wired Remote Controller
When the wireless remote controller is to be used, slide the switch (SW502) on the indoor unit control PCB to the ON position.
If this setting is not made, an alarm will occur. (The operation lamp on the display blinks.)
Reverse side view of Decorative Panel
Remove 3 screws and panel cover
Air conditioner
unit
Ceiling
Decorative
panel
Fig. 1-144
Wiring
Panel cover
1-399
Example of IMPROPER installation
Cool air
leakage
Air
(no good)
LM (CN033)
WL (CN130)
Catcher
PCB inside panel cover
Air conditioner
unit
Ceiling
Decorative
panel
Fig. 1-145
Ground screw
Fig. 1-146
Catcher
Fig. 1-147
Slide
Setting status
ON: Wireless: main, Wired: sub
OFF: Wired: main, Wireless: sub
(at shipment)
1