SELECTING THE LOCATION FOR THE INDOOR UNIT
5-1. Required Minimum Space for Installation and Service
Provide a check port on the piping side ceiling for repair and maintenance.
Install the indoor unit once the following conditions are satisfied and after receiving the customer approval.
1.
The indoor unit must be within a maintenance space.
2.
The indoor unit must be free from any obstacles in path of the air inlet and outlet, and must allow spreading of air
throughout the room.
Top view
(Uint : mm)
Inspection hole
(600 x 600)
600
<Front>
If the height from the floor to ceiling exceeds three meters, air flow distribution deteriorates and the effect is decreased.
POSITION OF SUSPENSION BOLT
A
B
Table 1-11
TYPE
S-36PN1E5A
S-45PN1E5A
S-50PN1E5A
S-60PN1E5A
S-71PN1E5A
S-100PN1E5A
S-125PN1E5A
S-140PN1E5A
Control box
600
Unit: mm
A
B
C
D
E
840
780
523
64
650
1060
1000
523
64
650
1260
1200
523
64
650
Front view
Above 250cm
Apply a joint-canvas between the unit and duct to
absorb unnecessary vibration.
Install the unit leaning to a drainage hole side as a
figure for easy water drainage.
CAUTION
Remove the absorber at air
return hole before installation.
Absorber
1-382
Fig. 1-108
1 ~ 3mm
Drainage hole
Fig. 1-109