Panasonic S-36PU1E5A Service Manual page 307

Table of Contents

Advertisement

(Wiring procedure)
(1)
Connect the remote controller to the indoor unit remote control wiring terminal board (1, 2).
(Remote control wiring)
(2) Connect the indoor units (U1, U2) and the outdoor units (1, 2). Connect the other outdoor units and indoor
units (with different refrigerant systems) in the same way. (Inter-unit control wiring) Connect the remote control
communication wiring to the indoor units (U1, U2) for each refrigerant system. (Inter-unit control wiring)
(3) Connect the remote control communication wiring (2 wires) from the remote control wiring terminal board
(1, 2) on the indoor unit (unit where the remote controller is connected) to the remote controller terminal board
(1, 2) on the other indoor units. (Remote control communication wiring)
(4) Turn ON both the indoor and outdoor unit power and perform automatic address setting from the remote
controller.
(For the automatic address setting procedure, refer to section "Automatic address setting using the remote
controller".)
NOTE
* Models with auxiliary heaters cannot be used for crossover wiring of the indoor unit power wires.
(Use a pull box to divide the wiring.)
Be sure to use the indoor unit temperature sensor (body sensor) when using this control. (Status at shipment.)
Setting the outdoor unit system addresses
For basic wiring diagram 2 (Set the system addresses: 1, 2, 3...)
Outdoor unit control PCB
System address rotary switch
(Set to "0" at time of shipment)
System address rotary switch
System address
10s 20s
DIP switch
ON
ON
OFF
1
2
HIC
Temperature
sensor
Up side
C2(CN020,WHT)
MOV(CN025,WHT)
63PH(CN004,RED)
Bottom
side
AUTO ADD(CN041)
System address
Rotary switch(S002)
TERMINAL (CN003)
JP007
System address
DIP switch (S003)
RC-P(CN032,RED)
LED1
LED2
PUMP DOWN(CN042)
EEPROM(IC006)
C1(CN021,BLK)
TO(CN022,WHT)
TD,TS(CN023,WHT)
SILENT MODE(CN028,WHT)
RC-P(CN034,RED)
FAN(CN030,WHT)
ROM(CN012,WHT)
OC(CN013,BLU)
EMG(CN014,BRN)
20S(CN09,WHT)
FUSE(30A,F003)
1-297
System address
System address
No.
(2P DIP switch)
ON
0 Automatic address
(Setting at shipment = "0")
ON
1 (If outdoor unit is No. 1)
ON
2 (If outdoor unit is No. 2)
10s digit ON
ON
11 (If outdoor unit is No. 11)
20s digit ON
ON
21 (If outdoor unit is No. 21)
10s digit and 20s
ON
30 (If outdoor unit is No. 30)
System address
10s digit
1s place
(Rotary switch)
Both OFF
"0" setting
ON
1
2
OFF
Both OFF
"1" setting
ON
1
2
OFF
Both OFF
"2" setting
ON
1
2
OFF
"1" setting
ON
1
2
OFF
"1" setting
ON
1
2
OFF
digit ON
"0" setting
ON
1
2
OFF
1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents