HOW TO INSTALL THE INDOOR UNIT
Low Silhouette Ducted Type (Type F1)
4-1. Required Minimum Space for Installation and Service
This air conditioner is usually installed above the ceiling so
that the indoor unit and ducts are not visible. Only the air
intake and air outlet ports are visible from the unit bottom.
The minimum space for installation and service is shown in
Fig. 1-90 and Table 1-7.
Table 1-7
Type
36, 45, 50
A (Length)
It is recommended that space be provided (450 × 450 mm)
for checking and servicing the electrical system.
The detailed dimensions of the indoor unit is shown in Fig.
1-91 and Table 1-8.
Table 1-8
Type
36, 45, 50
60, 71
100, 125, 140
172
60, 71
100, 125, 140
867
1,067
A
B
867
800
450 (Pitch 150 × 3)
1,067
1,000
750 (Pitch 150 × 5)
1,467
1,400
1,050 (Pitch 150 × 7)
Air intake port side
j
g
A (Suspension bolt pitch)
e
33.4
D
h
E (Flange O.D.)
54
Air outlet duct side
min.250
Unit: mm
1,467
C
D
E
71
592
21
792
71
1,192
B
Inspection
access
450 × 450
(Field supply)
(150)
C
D
154
33.4
1-370
A (Suspension bolt pitch)
Indoor unit
Unit: mm
F
12
16
20
a) Refrigerant tubing joint (liquid tube)
b) Refrigerant tubing joint (gas tube)
c) Upper drain port VP25 (O.D. 32 mm)
200 flexible hose supplied
d) Bottom drain port VP25 (O.D. 32 mm)
e) Suspension lug (4 – 12 × 30 mm)
f ) Power supply outlet
g) Fresh air intake port (ø150 mm)
h) Flange for flexible air outlet duct
i ) Electrical component box
j ) Filter
290
255
70
23
140
a
Unit: mm
Electrical
component box
Inspection
access
450 × 450
Refrigerant
tubing
Min.650
Fig. 1-90
f
i
c
d
26.1
90
b
23
Unit: mm
Fig. 1-91