SiENBE12-620

5.23 Radiation Fin Temperature Rise

L4
remote control
Display
Outdoor Unit LED
A
Display
Method of
A radiation fin temperature rise is detected by checking the radiation fin temperature being
Malfunction
detected by the fin thermistor with the compressor on.
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Service Diagnosis
1
2
3
4
5
1
1
1
The radiation fin temperature with the compressor on is above 103°C.
The error is cleared when the temperature drops below 95°C.
If a radiation fin temperature rise takes place 255 times successively, the system will be shut
down.
The error counter will reset itself if this or any other error does not occur during the following
60-minute compressor running time (total time).
Fin temperature rise due to defective outdoor unit fan
Fin temperature rise due to short-circuit
Fin thermistor defective
Connector in poor contact
Outdoor unit PCB defective
L4
4
Troubleshooting
243