Instruction
Be sure the air conditioner is electrically grounded.
Do not connect the grounding conductor to a gas pipe,
water pipe, lightning arrester and the grounding conductor
for a telephone.
Imperfect grounding work may result in an electric shock.
Execute complete drain piping for perfect drainage.
Incomplete piping may result in a water leakage.
The appliance is not intended for use by young
children or infirm persons without supervision. Young
children should be supervised to ensure that they do
not play with the appliance.
1. Operation range
If the temperature or the humidity is beyond the following
conditions, safety devices may work and the air
conditioner may not operate, or sometimes, water may
drop from the indoor unit.
Cooling
INDOOR
OUTDOOR UNIT
TEMPERA-
TURE
DB 18 to 33 80% or
R35 · 45 · 60
WB 12 to 24
DB 18 to 33 80% or
RY35 · 45 · 60
WB 12 to 24
R71 · 100 · 125
DB 21 to 35 80% or
RP71 · 100 · 125
WB 14 to 25
REP71 · 100 · 125
RY71 · 100 · 125
DB 18 to 35 80% or
RYP71 · 100 · 125
WB 12 to 25
RYEP71 · 100 · 125
DB 21 to 35 80% or
RZP71 · 100 · 125
WB 14 to 25
DB 18 to 37 80% or
RQ71 · 100 · 125
WB 12 to 28
DB 18 to 37 80% or
RR71 · 100 · 125
WB 12 to 28
DB 18 to 37 80% or
RZQ71 · 100 · 125 ·
140
WB 12 to 28
RS50 · 60
DB 21 to 32 80% or
RKS35 · 50 · 60
WB 14 to 23
RXS35 · 50 · 60
3MKS50
DB 21 to 32
4MKS58 · 75 · 90
3MXS52 · 2MXS52
WB 14 to 23
4MXS68 · 80
DB 21 to 32 80% or
RMKS112 · 140 · 160
RMXS112 · 140 · 160
WB 14 to 23
194
OUTDOOR
TEMPERA-
HUMID-
TURE
ITY
DB – 15 to 46
below
DB – 5 to 46
below
DB – 15 to 46
below
DB – 5 to 46
below
DB – 5 to 50
below
DB – 5 to 46
below
DB – 15 to 46
below
DB – 15 to 50
below
DB – 10 to 46
below
80% or
DB – 10 to 46
below
DB – 5 to 46
below
HEATING
INDOOR
OUTDOOR UNIT
TEMPERATURE
RY35 · 45 · 60
DB
RY71 · 100 · 125
RYP71 · 100 · 125
DB
RYEP71 · 100 · 125
RZP71 · 100 · 125
DB
RQ71 · 100 · 125
DB
RZQ71 · 100 · 125 ·
DB
140
RXS35 · 50 · 60
DB
3MXS52 · 2MXS52
DB
4MXS68 · 80
RMXS112 · 140 · 160 DB
DB: Dry bulb temperature (°C)
DB: Dry bulb temperature (°C)
WB: Wet bulb temperature (°C)
The setting temperature range of the remote control is 16°C to
32°C.
2. Installation site
Regarding places for installation
Is the air conditioner installed at a well-ventilated
place where there are no obstacles around?
Do not use the air conditioner in the following places.
a. Filled with much mineral oil such as cutting oil.
b. Where there is much salt such as a beach area.
c. Where sulfured gas exists such as a hot-spring resort.
d. Where there are considerable voltage fluctuations such
as a factory or plant.
e. Vehicles and vessels.
f. Where there is much spray of oil and vapor such as a
cookery, etc.
g. Where there are machines generating electromagnetic
waves.
h. Filled with acid and/or alkaline steam or vapor.
Is a snow protection measure taken?
For details, consult your dealer.
Regarding wiring
All wiring must be performed by an authorized
electrician.
To do wiring, ask your dealer. Never do it by yourself.
SiENBE12-620
OUTDOOR
TEMPERATURE
DB
– 9 to 21
15 to 27
WB – 10 to 15.5
DB
– 9 to 21
15 to 27
WB – 10 to 15.5
DB
– 14 to 21
15 to 27
WB – 15 to 15.5
DB
– 9 to 21
10 to 27
WB – 10 to 15
DB
– 19.5 to 21
10 to 27
WB – 20 to 15.5
DB
– 14 to 24
10 to 30
WB – 15 to 18
DB
– 14 to 21
10 to 30
WB – 15 to 15.5
DB
– 14 to 21
10 to 30
WB – 15 to 15.5
System Configuration