Daikin E-Series Service Manual page 249

Hide thumbs Also See for E-Series:
Table of Contents

Advertisement

Troubleshooting
Troubleshooting
Check No.06
Refer to P.255
3 error if discharge pipe
hermistor temperature is
maller than condenser
hermistor temperature
P4 : Radiation fin thermistor
J3 : Discharge pipe thermistor
J6 : Outdoor unit heat exchanger thermistor
J8 : Liquid pipe thermistor
J9 : Gas pipe thermistor
H9 : Outdoor temperature thermistor
240
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Turn on the power again.
Error displayed again
on remote controller?
YES
Connector or thermistor
disconnected?
NO
Check No.
06
Check the thermistor resistance
value.
Normal?
YES
Cooling: Outdoor unit heat
exchanger thermistor
Heating: Indoor unit heat
exchanger thermistor
Check No.
06
Check the indoor unit heat
exchanger thermistor resistance
value in the heating mode.
Indoor unit
heat exchanger thermistor
functioning?
YES
NO
YES
NO
NO
SiENBE12-620
Reconnect.
Reconnect.
Replace defective one(s) of
the following thermistors.
Radiation fin thermistor
Discharge pipe
thermistor
Outdoor unit heat
exchanger thermistor
Liquid pipe thermistor
Gas pipe thermistor
Outdoor temperature
thermistor
Replace the following thermis
Indoor unit heat
exchanger thermistor
Replace the outdoor unit
PC board. (Replace the
indoor unit PC board.)
(R4718)
Service Diagnosis

Advertisement

Table of Contents
loading

Table of Contents