A7" Indoor Unit: Malfunction Of Swing Flap Motor (Ma) - Daikin R410As Service Manual

Vrv heat pump 50hz
Table of Contents

Advertisement

Si39-302
" A7 " Indoor Unit:
2.5
A7
Remote
Controller
Display
Applicable
FXCQ, FXAQ, FXFQ, FXHQ, FXKQ
Models
Method of
Utilizes ON/OFF of the limit switch when the motor turns.
Malfunction
Detection
Malfunction
When ON/OFF of the microswitch for positioning cannot be reversed even though the swing flap
motor is energized for a specified amount of time (about 30 seconds).
Decision
Conditions
!
Supposed
!
Causes
!
!
Troubleshooting
Malfunction of Swing Flap Motor (MA)
Defect of swing motor
Defect of connection cable (power supply and limit switch)
Defect of air flow direction adjusting flap-cam
Defect of indoor unit PC board
Troubleshooting by Indication on the Remote Controller
161