Low Pressure Protection Control - Daikin R410As Service Manual

Vrv heat pump 50hz
Table of Contents

Advertisement

Protection Control
4.2

Low Pressure Protection Control

This low pressure protection control is used to protect compressors against the transient
decrease of low pressure.
[In cooling operation]
#
Low pressure not limited
Pe<0.35MPa
Low pressure limited
All STD compressors
Pe<0.25MPa
Master unit:52 Hz + OFF + OFF
Slave unit:Stop
Pe<0.07MPa
Low pressure standby
[In heating operation]
#
Pe<0.16 MPa
124 Hz + OFF + OFF
Pe<0.16 MPa
Pe<0.13 MPa
52 Hz + OFF + OFF
84
In the case of multi-outdoor-unit system, the entire system performs this control in the
following sequence.
Pe>0.40MPa
stop.
In the case of multi-outdoor-unit system, each outdoor unit performs this control
individually in the following sequence.
Low pressure not limited
&
Low pressure limited
Pe<0.07 MPa
Low pressure standby
Pe: LP pressure sensor detection
value for master unit
When occurring 3 times within 30 min.,
the malfunction code " E4 " is output.
Pe: LP pressure sensor detection
Pe >0.25 MPa
INV upper limit frequency = 210 Hz
Pe>0.19 MPa
INV upper limit frequency: 1-step /
20 sec up from current compressor
frequency
When occurring 3 times within 30 min.,
the malfunction code "E4" is output.
value for each outdoor unit
Si39-302
Function

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents