Special Control; Startup Control - Daikin R410As Service Manual

Vrv heat pump 50hz
Table of Contents

Advertisement

Special Control

3.

Special Control

3.1

Startup Control

3.1.1 Startup Control in Cooling Operation
Actuator
Compressor
Outdoor unit fan
Four way valve
Main motorized valve (EV1)
Subcooling motorized valve (EV2)
Hot gas bypass valve (SVP)
Oil equalization valve (SVO)
Receiver gas charging valve (SVL)
Receiver gas discharging valve (SVG)
Non-operating unit gas discharging
valve (SVSG)
Non-operating unit liquid pipe stop
valve (SVSL)
Ending conditions
In the case of multi-outdoor-unit system, both master and slave units perform the operations listed in the table
above.
Actuators are based on RXYQ16M.
3.1.2 Startup Control in Heating Operation
Actuator
Compressor
Outdoor unit fan
Four way valve
Main motorized valve (EV1)
Subcooling motorized valve (EV2)
Hot gas bypass valve (SVP)
Oil equalization valve (SVO)
Receiver gas charging valve (SVL)
Receiver gas discharging valve (SVG)
Non-operating unit gas discharging
valve (SVSG)
Non-operating unit liquid pipe stop
valve (SVSL)
Ending conditions
In the case of multi-outdoor-unit system, both master and slave units perform the operations listed in the table
above.
Actuators are based on RXYQ16M.
74
Operation
Differential pressure control
High pressure control
OFF
0 pls
0 pls
ON
ON
OFF
OFF
OFF
ON
• 200 sec.
or
• Pc - Pe>0.4 MPa
Operation
Differential pressure control
STEP9
ON
200 pls
0 pls
ON
ON
OFF
OFF
OFF
ON
• 200 sec.
or
• Pc - Pe>0.4 MPa
Remarks
Compressor operating frequency
increases by 1 step / 20 sec until
Pc - Pe>0.4 MPa.
Initial compressor operating frequency
is set to STEP 1.
1-step increase with Pc>2.2 MPa
1-step decrease with Pc<1.8 MPa
 (RXYQ5M : 1400pls)
In the case of multi-outdoor-unit
system, this valve repeats ON/OFF
operation at regular intervals of time to
equalize the oil level of each outdoor
unit.
Remarks
Compressor operating frequency
increases by 1 step / 20 sec until
Pc - Pe>0.4 MPa.
In the case of multi-outdoor-unit
system, this valve repeats ON/OFF
operation at regular intervals of time to
equalize the oil level of each outdoor
unit.
Si39-302