Outline of Control (Indoor Unit)
6. Outline of Control (Indoor Unit)
6.1
Drain Pump Control
1. The drain pump is controlled by the ON/OFF buttons (4 button (1) - (4) given in the figure
6.1.1 When the Float Switch is Tripped While the Cooling Thermostat is
ON:
∗
the indoor unit heat exchanger when the thermostat goes off during cooling operation.
6.1.2 When the Float Switch is Tripped During Cooling OFF by
Thermostat:
92
below).
1. The objective of residual operation is to completely drain any moisture adhering to the fin of
Si39-302
Function