Other Control
• With RXYQ14M and 16M, if INV compressor is inhibited from operating, only 1 STD
compressor can operate for reasons of oil equalization.
• With RXYQ14M and 16M, STD1 compressor cannot be inhibited from operating for reasons of
oil equalization.
• When 1 outdoor unit is installed (with RXYQ8M to 16M), automatic backup operation cannot
be performed.
5.2.3 In The Case of Multi-Outdoor-Unit System (RXYQ18 to 48M)
Emergency operation with settings in service mode
Make the following settings with the master unit. (Setting with the slave unit becomes disabled.)
• To inhibit the master unit from operating → Set
setting mode 2 from No. 38 to No. 2.
• To inhibit the slave unit 1 from operating → Set
setting mode 2 from No. 39 to No. 2.
90
Automatic backup operation
With multi-outdoor-unit system, if a certain outdoor unit system malfunctions (i.e., the system
stops and indoor unit remote controller displays the malfunction), by resetting the system with
the indoor unit remote controller, the applicable outdoor unit is inhibited from operating for 8
hours, thus making it possible to perform emergency operation automatically.
However, in the event any of the following malfunctions occurs, automatic backup operation
can be performed.
Malfunctions under which automatic backup operation can be performed:
• E3, E4, E5, E7
• F3
• H7, H9
• J2, J3, J5, J6, J7, J9, JA, JC
• L3, L4, L5, L8, L9, LC
• U2, UJ
"Inhibition of operation" is set with each outdoor unit.
Discriminate the operating status of the master unit/slave units through the following LED
display.
LED display (7:ON 7:OFF 9:Blink)
H1P---H7P H8P
Master:
7777777
77
7777 7
Slave 1:
7777777 9
Slave 2:
7777777 7
(Factory set)
(Procedure)
(1) Press and hold the MODE button (BS1) for 5 sec. or
more.
(2) Press the SET button (BS2) 38 times.
(3) Press the RETURN button (BS3) once.
(4) Press the SET button (BS2) once.
(5) Press the RETURN button (BS3) twice.
(6) Press the MODE button (BS1) once.
(Procedure)
(1) Press and hold the MODE button (BS1) for 5 sec. or
more.
(2) Press the SET button (BS2) 39 times.
(3) Press the RETURN button (BS3) once.
(4) Press the SET button (BS2) once.
(5) Press the RETURN button (BS3) twice.
(6) Press the MODE button (BS1) once.
LED display (7:ON 7:OFF 9:Blink)
H1P---H7P
7777777
7777
77777
(Factory set)
7777779
7777797
7777777
7777777
77
LED display (7:ON 7:OFF 9:Blink)
H1P---H7P
7777777
7777
77777
(Factory set)
7777779
7777797
7777777
7777777
77
Si39-302