Daikin R410As Service Manual page 302

Vrv heat pump 50hz
Table of Contents

Advertisement

Si39-302
2. Torque wrench
!
2 Dimension B
!
2 Change of dimension B
3. Vacuum pump with check valve
!
2 Discharge speed
2 Suction port UNF7/16-20(1/4 Flare)
!
2 Equipped with function to prevent reverse oil flow
2 Previous vacuum pump can be used by installing adapter.
Precautions for New Refrigerant (R410)
Specifications
Nominal size
Class-1
1/2
24
5/8
27
No change in tightening torque
No change in pipes of other sizes
Differences
Only 1/2", 5/8" are extended
Specifications
50 l/min (50Hz)
60 l/min (60Hz)
UNF1/2-20(5/16 Flare) with adapter
Differences
Precautions for New Refrigerant (R410)
Class-2
26
29
For class-1: R407C
For class-2: R410A
Dimension B
Vacuum pump adapter
Reverse flow preventive
vacuum adapter
)
Maximum degree of vacuum
–100.7 kpa ( 5 torr – 755 mmHg)
Unit:mm
Previous
24
27
291