Si39-302
Connectable indoor unit
Type
Ceiling mounted
FXCQ
cassette type
(Double flow)
Ceiling mounted
cassette type
FXZQ
(Multi flow)
600×600
Ceiling mounted
FXFQ
cassette type
(Multi flow)
Ceiling mounted
FXKQ
cassette corner
Ceiling mounted
FXSQ
built-in type
Ceiling mounted
FXMQ
duct type
Ceiling
FXHQ
suspended type
Wall mounted
FXAQ
type
Floor standing
FXLQ
type
Concealed Floor
FXNQ
standing type
Indoor unit capacity
New refrigerant model code
Selecting model capacity
Equivalent output
Use the above tables to determine the capacities of indoor units to be connected. Make sure the
total capacity of indoor units connected to each outdoor unit is within the specified value (kW).
!
!
General Information
20M
25M
32M
40M
20M
25M
32M
40M
25M
32M
40M
25M
32M
40M
20M
25M
32M
40M
40M
32M
20M
25M
32M
40M
20M
25M
32M
40M
20M
25M
32M
40M
P20
P25
P32
type
type
type
2.2
2.8
3.5
kW
kW
kW
0.8HP
1HP
1.25HP
The total capacity of connected indoor units must be within a range of 50 to 130% of the
rated capacity of the outdoor unit.
In some models, it is not possible to connect the maximum number of connectable indoor
units. Select models so the total capacity of connected indoor units conforms to the
specification.
Model Name
50M
63M
80M
50M
50M
63M
80M
100M 125M
63M
50M
63M
80M
100M 125M
50M
63M
80M
100M 125M 200M 250M
63M
100M
50M
63M
50M
63M
50M
63M
P40
P50
P63
type
type
type
4.5
5.6
7.0
kW
kW
kW
1.6HP
2.0HP
2.5HP
3.2HP
Model Selection
Power Supply
125M
P80
P100
P125
P200
type
type
type
type
9.0
11.2
14.0
22.4
kW
kW
kW
4HP
5HP
8HP
VE
P250
type
28.0
kW
kW
10HP