Indoor Unit: Malfunction Of Capacity Determination Device - Daikin VRV K Manual

Table of Contents

Advertisement

SI-95.BOOK Page 84 Friday, March 31, 2000 10:59 AM
Troubleshooting
2.8

Indoor Unit: Malfunction of Capacity Determination Device

A A A A J J J J
Remote controller
display
I You have forgotten to install the capacity setting adaptor.
Supposed Causes
I Defect of indoor unit PC board
Troubleshooting
84
The indoor
NO
unit PC board was replaced
with a replacement
PC board.
YES
The indoor
unit is a model that
NO
requires installation of a
capacity setting adaptor when
replacing the PC
board.
YES
Si-95
Replace the indoor unit PC board.
Replace the indoor unit PC board.
Install a capacity setting adaptor.
(VF035)