1.10 Indoor Field Setting

Making a field setting
Field settings must be made by remote controller if optional accessories have been installed on the indoor
unit, or if the indoor unit or HRV unit's individual functions have been modified.
1.10.1 Wired Remote Controller
1. When in the normal mode, push the
2. Select the desired "mode No." with the
3. During group control and you want to set by each individual indoor unit (when mode No. 20, 21, 22, 23,
4. Push the
5. Push the
6. Push the timer
7. Push the
1.10.2 Wireless Remote Controller
1. When in the normal mode, push the
2. Select the desired "mode No." with the
3. Pushing the
4. Pushing the
5. Push the timer
6. Push the
Test Operation Inverter K Series
the "field set mode."
25 has been selected), push the time mode
Note: This operation is not required when setting as a group.
button and select the first code No.
button and select the second code No.
button one time and "define" the currently set contents.
button to return to the normal mode.
the "field set mode."
button, select the first code No.
button, select the second code No.
button and check the settings.
button to return to the normal mode.
button for 4 seconds or more, and operation then enters
button.
button and select the "indoor unit No." to be set.
button for 4 seconds or more, and operation then enters
button.
Test Operation
61