Compressor Capacity Control - Daikin VRV K Manual

Table of Contents

Advertisement

SI-95.BOOK Page 31 Friday, March 31, 2000 10:59 AM
Si-95

1.16 Compressor Capacity Control

Pressure is sampled every 20 seconds by pressure sensors, and the inverter + standard compressor is
controlled in 20 stages by microcomputer.
Functions Inverter K Series
Commercial power supply
Commercial power supply
compressor (off)
compressor (full load)
Frequency
30Hz+OFF
34Hz+OFF
38Hz+OFF
42Hz+OFF
48Hz+OFF
54Hz+OFF
60Hz+OFF
68Hz+OFF
76Hz+OFF
86Hz+OFF
96Hz+OFF
106Hz+OFF
106Hz+ON
116Hz+ON
Min. output
Frequency
38Hz+ON
48Hz+ON
60Hz+ON
76Hz+ON
86Hz+ON
96Hz+ON
Max. output
(VE005)
Functions
31