SI-95.BOOK Page 122 Friday, March 31, 2000 10:59 AM
Troubleshooting (Inverter)
4.8

Outdoor Unit: Inverter Over-Ripple Protection

P P P P 4 4 4 4
Remote Controller
Display
I Defect of radiator fin temperature sensor
Supposed Causes
I Defect of inverter unit
Troubleshooting
122
Turn on
again after letting 30
minutes or more pass after
occurrence of
malfunction.
"P4" occurs again.
Replace the radiator fin thermistor.
(VF070)