SI-95.BOOK Page 76 Friday, March 31, 2000 10:59 AM
Diagnosis by Malfunction Code
1.2

Failure Diagnosis

1.2.1
Inverter Failure Diagnosis
Malfunction code
1.2.2
Failure Diagnosis for Optional Controllers for Centralized Control
Malfunction code
76
Malfunction contents
L4
Outdoor unit: Malfunction of inverter radiating fin temperature rise
L5
Outdoor unit: Inverter instantaneous over-current
L8
Outdoor unit: Inverter electronic thermal, compressor overload
L9
Outdoor unit: Inverter stall prevention, compressor seizing
LC
Outdoor unit: Malfunction of transmission between inverter and
control PC board
P1
Outdoor unit: Inverter over-ripple protection
P4
Outdoor unit: Malfunction of inverter radiating fin temperature rise
sensor
Optional controllers for
centralized control
UE
Central remote controller
Schedule timer
M1
Central remote controller
Schedule timer
M8
Central remote controller
Schedule timer
MA
Central remote controller
Schedule timer
MC
Central remote controller
Schedule timer
Unified ON/OFF controller
Malfunction contents
Malfunction of transmission between central remote
controller and indoor unit
PC board defect
Malfunction of transmission between optional
controllers for centralized control
Improper combination of optional controllers for
centralized control
Address duplication, improper setting
Operation lamp blinks
Display "under host computer integrate control" blinks
(repeats single blink)
Display "under host computer integrate control" blinks
(repeats double blink)
Troubleshooting Inverter K Series