SI-95.BOOK Page 118 Friday, March 31, 2000 10:59 AM
Troubleshooting (Inverter)
4.4

Outdoor Unit: Inverter Stall Prevention, Compressor Seized

L L L L 9 9 9 9
Remote Controller
Display
I Defect of compressor
Supposed Causes
I Pressure differential start
I Defect of inverter unit
Troubleshooting
118
The
difference
between high and low
NO
pressure when starting is less
than 2 kg / cm² =
(0.196 MPa).
YES
Disconnect
the the connection between
the compressor
and inverter.
Inverter
output voltage
check Inverter output
NO
voltage is not balanced.
(Normal if within ±8 V [Y1])
(Note) Must be
measured when
frequency
is stable.
After turning
on again, "L9" blinks
again.
YES
Si-95
Unsatisfactory pressure equalization
Check refrigerant system.
Replace the inverter unit.
Compressor inspection
Inspect according to the diagnosis
procedure for odd noises, vibration and
operating status of the compressor.
(VF066)