Equalized Oil Level Operation (Equalized Oil Level Between Twin Compressors) - Daikin VRV K Manual

Table of Contents

Advertisement

SI-95.BOOK Page 19 Friday, March 31, 2000 10:59 AM
Si-95
1.6
Equalized Oil Level Operation
(Equalized Oil Level between Twin Compressors)
If using two compressors (8, 10Hp) connected in parallel, oil level equalizing is carried out for 5 minutes if
the cumulative running time of the standard compressor exceeds 2 hours in order to prevent lack of oil
cause by difference in pressure inside the dome due to drift, and then reverts to normal operation.
∗ If oil pressure equalization is not achieved during 5 minutes by stopping or step down control, oil pressure
equalization is carried out when the standard compressor starts running.
With an inverter compressor operation, however, if the standard compressor remains off for 10 minutes,
the cumulative running time of the standard compressor is reset.
During equalized oil level operation with Y2R → ON, when low pressure < 2.0kg/cm
(Reset at low pressure > 3.0kg/cm
Functions Inverter K Series
Inverter compressor
106Hz
2
)
Standard compressor
OFF
2
, Y2S becomes ON.
Functions
19

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents