Generators; Magnetic Contactors And Starters; Starting Motor Limitamp Contactor; Load Gear And Collector Compartments - GE MS-6001B Maintenance Instructions Manual

Gas turbines with dln-1 combustion systems gas only
Hide thumbs Also See for MS-6001B:
Table of Contents

Advertisement

Inspection and Maintenance
Inspection and Maintenance Procedures

Magnetic Contactors and Starters

Check to see if the relay contacts are welded together by depressing the brown operator (actuator), located
at the top of the overload relay contact housing. When the relay is in a reset condition, an audible click
will be heard when the operator is depressed. This indicates that the contacts are operating normally.
A continuity check can also be made by disconnecting the control wiring from the terminals of the relay
and placing a bell set, or a resistance measuring instrument, in the circuit. Connecting either of these
across the relay terminals, will indicate the relay contact is closed until the contact-check operator is de-
pressed; interrupting the circuit.
Check the magnet mating surfaces and assure they are free from dust, dirt, oil and grease.
Check the silver contacts for wear. If the silver tip is worn, and the contact tip support is exposed, replace
the contacts. DO NOT FILE THE SILVER CONTACTS to clean off projections, nicks, scratches, etc.
Magnetic Relays
Check the contact surfaces for cleanliness, dirt, dust, oil and grease, etc.
Check the silver contacts for wear and replace them before the silver is completely gone. DO NOT FILE
THE SILVER CONTACTS to clean off projections, nicks, scratches, etc.
General Purpose Contactors
Inspect the arc chute for physical damage. Check the arcing horn clearances. Check the armature spring
adjustments, contact force, tie gaps and wires.
Starting Motor Limitamp Contactor (if applicable)
Over a period of time contactor bolts can loosen. This may cause tip misalignment and arcing. Periodic
inspection, preventative maintenance and cleaning can prevent contactor damage.
Disengage the contactor from the power stabs by moving it to the service position. Check all hardware
for looseness, check for loose electrical connections, blow off accumulations of dust, dirt and wipe base
clean, check contacts for general conditions, check magnet assembly and align if needed. Refer to the
Limitamp Devices tab in your Service Manual for further information.

GENERATORS

For Maintenance and Inspection Procedures for the generator refer to the Generator Maintenance section
of this Service Manual.

Load Gear and Collector Compartments

Make sure there are no loose fiberglass expansion joints in this compartment, that all interfaces between
the compartment and generator ends are watertight, and the seals are not damaged. If there is an accumu-
lation of dust or dirt, it should be cleaned out. Check the cooling air discharge vents to be sure they are
not clogged.