Input Wiring; Input Configuration - Delta DAC-1600 Installation Manual

Table of Contents

Advertisement

Delta Controls

Input Wiring

Inputs on the DAC-1600 controller follow the same general wiring requirements as other Delta Controls
products. Recommended cable types should be used as listed below. Refer to the Delta Controls Wiring
Guidelines for more details.
Recommended Cable Type
2 Conductor, 18 AWG, Unshielded
2 Conductor, 22 AWG, Shielded

Input Configuration

The input must be configured to accept the signal used by
the input device. Place the jumper for each input in the
correct location on the Input Type Selector Block. The
diagram to the right shows the factory default selection of
10 KΩ.
4-20mA 
For sensors that use a 4 to 20 mA signal.
10K
For 10 KΩ Thermistor temperature
sensors, as well as Dry Contact binary
inputs.
5V
For sensors that use a 0 - 5 VDC signal.
10V
For sensors that use a 0 -10 VDC signal.
Page 8 of 12
Where to Use
4-20mA, 10KΩ, and 10V input types
Inputs configured for 5V