9.3.2

Selecting power supply units

You are advised to use the devices in the following table. These devices meet the applicable
requirements of EN 60204-1.
Table 9-1
Recommendation for SITOP Power modular
Rated output current [A]
5
10
20
40
Table 9-2
Recommendation for Control Supply Module
Rated output current [A]
20
See catalog D21.2.
When an external power supply is used, e.g. SITOP, the ground potential must be
connected to the protective conductor system (DVC A).
AC Drive
Manual, (GH6), 07/2007 Edition, 6SL3097-2AL00-0BP2
Input voltage range [V]
2 AC 85-132/170 – 550
2 AC 85-132/176 – 550
3-ph. 320 – 550 V AC
3-ph. 320 – 550 V AC
Input voltage range [V]
3-ph. 380 V AC -10% (-15% <
1 min) to 3-ph. 480 V AC+10%
DC 300 – 800
WARNING
Cabinet Design and EMC for Components, Blocksize Format
Short-circuit current [A]
5.5
30 for 25 ms
23
46
Short-circuit current [A]
< 24
9.3 24 V DC supply voltage
Order No.
6EP1333-3BA00
6EP1334-3BA00
6EP1336-3BA00
6EP1337-3BA00
Order No.:
6SL3100-1DE22-0AA0