Connect Ups Using The I/O Connector - Omron NYB17-11 User Manual

Industrial box pc ny-series
Table of Contents

Advertisement

5-8-2

Connect UPS Using the I/O Connector

The I/O connector of the Industrial Box PC:
• receives the power status of the UPS with the UPS Mode Input when the Box PC has a Windows
operating system. For other operating systems this input is not functional.
• indicates the power status of the Box PC to the UPS with the Power Status Output.
Additional Information
• A UPS connection using the I/O connector is only possible for a Box PC with a Windows op-
erating system. For all other operating systems use the USB connector to connect the UPS.
Refer to 5-8-1 Connect UPS Using the USB Connector on page 5 - 52 for details.
• The Box PC does not react automatically to the UPS Mode Input.
A custom software program is required to shut down the Box PC when needed.
UPS Drivers and the required software is available.
• For Box PCs with Windows 10 or Windows 7 preinstalled:
• Drivers for the S8BA UPS are pre-installed
• Installation files and manual for the UPS Settings Utility are availabe in the installer directory
D:\OMRON-NY\Installers\UPS Settings Utility
• For all other Box PCs following software can be downloaded from the OMRON download site:
• Drivers for the S8BA UPS
• Installation files and manual for the UPS Settings Utility (Windows only)
Precautions for Safe Use
• Always use the recommended uninterruptible power supply (UPS) to prevent data loss and
other system file integrity issues caused by unexpected power interruption.
• Use an Omron S8BA UPS with the correct revision number to prevent improper system shut-
down.
• Correctly perform wiring and setting, and ensure that the shutdown by the UPS can be exe-
cuted.
Follow the steps below to connect the S8BA UPS to the I/O connector of the Box PC and to configure
it correctly.
Refer to 5-4-4 Wire the I/O Connector on page 5 - 37 for I/O Connector details.
1
Ensure the revision number of the UPS is correct.
Refer to 2-9-9 UPS on page 2 - 21 for more information.
2
For Box PCs that do not have Windows pre-installed: Download the above mentioned soft-
ware.
3
Wire the S8BA UPS.
(1) Wire the input of the UPS to the output of the Power Supply.
(2) Wire the output of the UPS to the power connector of the Box PC.
(3) Ground the UPS.
(4) Connect the Contact port of the S8BA UPS to the I/O port of the Box PC with the connec-
tion cable S8BW-02.
NY-series Industrial Box PC User's Manual (W553)
5 Installation
5
5 - 55

Advertisement

Table of Contents
loading

Table of Contents