Mitsubishi MELSEC-Q QD77MS User Manual page 386

Simple motion module
Table of Contents

Advertisement

Setting item
Cd.6
Restart command
: Refer to Section 5.7 "List of control data" for details on the setting details.
(6) When stopped with interpolation operation, write "1: Restarts" into
Cd.6
"
Restart command" for the reference axis, and then restart.
(7) If the PLC READY signal is changed from OFF to ON while stopped, restarting
is not possible.
If restart is requested, a warning "Restart not possible" (warning code: 104)
will occur.
(8) When the machine OPR and fast OPR is stopped, a error "OPR restart not
possible" (error code: 209) will occur and the positioning cannot restarts.
(9) If any of reference partner axes executes the positioning operation once after
interpolation operation stop, a warning "Restart not possible" (warning code:
104) will occur, and the positioning cannot restarts.
[3] Control data requiring setting
Set the following data to execute restart.
Setting
value
1
Set "1: Restarts".
[4] Starting conditions
The following conditions must be satisfied when restarting. (Assemble the
required conditions into the sequence program as an interlock.)
(1) Operation state
Md.26
"
Axis operation status" is "1: Stopped"
Chapter 6 Sequence Program Used for Positioning Control
Setting details
6 - 71
Buffer memory address
QD77MS2
QD77MS16
QD77MS4
1503+100n
4303+100n
n: Axis No.-1