X132: Digital Inputs/Outputs; Table 2-4 Terminal Block X132 - Siemens SINAMICS S120 Equipment Manual

Control units and additional system components
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

2.2.3.5

X132: Digital inputs/outputs

Table 2-4
Terminal block X132
Terminal
1
2
3
4
5
6
7
8
9
10
11
12
Max. connectable cross-section: 0.5 mm
Type: Spring-loaded terminal 1 (see Appendix A)
1) DI: digital input; DI/DO: digital input/output; M: electronic ground; M2: ground reference
Note
An open input is interpreted as "low".
The "fast inputs" can be used for position sensing.
To enable digital inputs (DI) 4 to 7 to function, terminal M2 must be connected. This can be
done as follows:
Connect the reference mass of the digital inputs, or a jumper to terminal M
(Notice this removes isolation for these digital inputs).
Note
If a momentary interruption in the voltage occurs in the 24 V supply, the digital outputs will
be deactivated until the interruption has been rectified.
Equipment Manual Control Units and Additional System Components
Equipment Manual, (GH1), 12/2004 Edition, 6SL3097-2AH00-0BP1
Name
1)
DI 4
DI 5
DI 6
DI 7
M2
M
DI/DO 12
DI/DO 13
M
DI/DO 14
DI/DO 15
M
2
2.2 Control Unit 320 (CU320)
Technical specifications
Voltage: -3 V to 30 V
Typical current consumption: 10 mA at 24 V DC
Isolation: The reference potential is terminal M2
Level (incl. ripple)
High level: 15 V to 30 V
Low level: -3 V to 5 V
Signal propagation times:
L → H 50 μs
H → L: 100 μs
As input:
Voltage: -3 V to 30 V
Typical current consumption: 10 mA at 24 V DC
Level (incl. ripple)
High level: 15 V to 30 V
Low level: -3 V to 5 V Terminal numbers 8, 10, and 11
are "fast inputs"
Terminal numbers 8, 10, and 11 are "fast inputs"
Signal propagation times for inputs/"fast inputs":
L → H: approx. 50 μs/5 μs
H → L: approx. 100 µs/50 µs
As output:
Voltage: 24 V DC
Max. load current per output: 500 mA
Continued-short-circuit-proof
Control Units
2-9