4.4.6
Technical specifications
Table 4-12
Technical specifications
Electronics power supply
Voltage
Current
Power loss
Max. ambient temperature up to an
altitude of 2000 m
Note:
As of an altitude of 2000 m, the max. ambient temperature decreases by 7° C every 1000 m.
PE/ground connection
Weight
4.5
Sensor Module Cabinet 30 (SMC30)
4.5.1
Description
The SMC30 evaluates encoder signals and transmits the speed, actual position value, rotor
position and, if necessary, the motor temperature and reference point via DRIVE-CLiQ to the
Control Unit.
TTL (to RS422 standard) and HTL rectangular signal sensors can be connected.
Table 4-13
Sensor type
TTL (bipolar) with 5 V sensor supply
TTL (bipolar) with 24 V sensor supply
HTL (unipolar/bipolar ) with 24 V sensor supply
Table 4-14
Sensor type
TTL*
HTL unipolar
HTL bipolar
*For TTL sensor on X520 → Remote Sense → 100 m
Equipment Manual Control Units and Additional System Components
Equipment Manual, (GH1), 12/2004 Edition, 6SL3097-2AH00-0BP1
Unit
V
DC
A
DC
W
° C
On housing with M4/1.8 Nm screw
kg
Connectable sensors with supply voltage
Maximum signal cable lengths
Encoder System Connection
4.5 Sensor Module Cabinet 30 (SMC30)
Value
24 DC (20.4 – 28.8)
Max. 0.4
<10
55
0.8
to X520 (SUB-D)
to X521/X531 (terminal
block)
Yes
Yes
Yes
No
No
Yes
Maximum signal cable length in m
100
100
300
4-19