2.2.3.12

Description of the LEDs on the Control Unit

Table 2-10
Description of the LEDs on the Control Unit
LED
Color
RDY
-
(READY)
Green
Red
Green
Red
Orange
DP1
-
(PROFIBUS
cyclic operation)
Green
Red
OPT
-
(OPTION)
Green
Red
MOD
-
Green
Equipment Manual Control Units and Additional System Components
Equipment Manual, (GH1), 12/2004 Edition, 6SL3097-2AH00-0BP1
State
Description
OFF
Electronics power supply outside permissible tolerance range
Continuous
The component is ready for operation and cyclic DRIVE-CLiQ
communication is taking place.
Flashing
Writing to CompactFlash Card
2 Hz
Continuous
At least one fault is present in this component.
Flashing
CompactFlash Card has not been inserted.
0.5 Hz
Boot error (e.g. firmware cannot be loaded to the RAM).
Flashing
Control Unit 320 is ready for operation.
0.5 Hz
No software licenses for device.
Continuous
DRIVE-CLiQ communication is being established.
Flashing
Unable to load firmware to RAM
0.5 Hz
Flashing
Firmware CRC error
2 Hz
OFF
Cyclic communication is not (yet) running.
Note:
The PROFIBUS is ready for communication when the Control Unit is
ready for operation (see RDY LED).
Continuous
Cyclic communication is running.
Flashing
Cyclic communication is not yet running fully.
0.5 Hz
Possible reasons:
The master is not transmitting setpoints.
No global control (GC) or master sign-of-life is transmitted during
isochronous operation.
Continuous
Cyclic communication has been interrupted.
OFF
Electronics power supply outside permissible tolerance range.
The component is not ready for operation.
The Option Board is missing or an associated drive object has not
been created.
Continuous
Option Board ready for operation
Flashing
Depends on the Option Board used
0.5 Hz
Continuous
At least one fault is pending in this component.
The Option Board is not ready (e.g. after power ON).
OFF
Reserved
Continuous
Reserved